Variable
Name
Data
Range
Description
IF Error
Config.
Value
Double Class: 0 to 3
This parameter sets the default class
assignment for points in the double input
dataset. All points not specified in the
override section of the configuration will be
assigned to this class. For class 0, no
events will be generated for the points.
0
AI Deadband: 0 to 32767 This value sets the global deadband for all
analog input points not specified in the
override section. Events will be generated
when the last saved value exceeds the limit
of this parameter.
32767
Float
Deadband:
Any valid
floating-
point value
This value sets the global deadband for all
float input points not specified in the
override section. Events will be generated
when the last saved value exceeds the limit
of this parameter.
0
Double
Deadband:
Any valid
double
floating-
point value
This value sets the global deadband for all
double input points not specified in the
override section. Events will be generated
when the last saved value exceeds the limit
of this parameter.
0
Select/Operat
e Arm Time:
1 to 65535 Time period after select command received
in which operate command will be
performed. After the select command is
received, the operate command will only be
honored if it arrives within this period of
time.
2000
Write Time
Interval:
0 to 1440
minutes
Time interval to set the need time IIN bit
(0=never), which will cause the master to
write the time. Stored in milliseconds in the
module memory.
1440
Data Link
Confirm
Mode:
N, S or A
IED can request acknowledgement from
master station when sending data. The
codes are as follows: N=Never,
S=Sometimes, A=Always
N
Data Link
Confirm Tout:
1 to 65535 Time period to wait for Master Data Link
confirmation of last frame sent. This time is
in milliseconds. This parameter is only used
if the frame is sent with confirmation
requested.
1
Data Link Max
Retry:
0 to 255
Maximum number of retries at the Data Link
level to obtain a confirmation. If this value is
set to 0, retries are disabled at the data link
level of the protocol. This parameter is only
used if the frame is sent with confirmation
requested.
255
App Layer
Confirm Tout:
1 to 65535 Event data contained in the last response
may be sent again if not confirmed within
the millisecond time period set. If
application layer confirms are used with
data link confirms, ensure that the
application layer confirm timeout is set long
enough.