ProSoft Technology MVI94-DNP User Manual
Page 108

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 108 of 131
ProSoft Technology, Inc.
December 17, 2010
OBJECT
REQUEST
RESPONSE
Obj
Var Description
Func
Codes
Qual
Codes
(hex)
Func
Code
s
Qual
Codes
(hex)
Data
Size
(bits
)
NOTES
1
32-Bit Analog Change Event
Without Time
1
06, 07,
08
17, 28
40
Master will generate and
process this variation
2
16-Bit Analog Change Event
Without Time
1
06, 07,
08
17, 28
24
Master will generate and
process this variation
3
32-Bit Analog Change Event
With Time
1
06, 07,
08
17, 28
88
Master will generate and
process this variation
4
16-Bit Analog Change Event
With Time
1
06, 07,
08
129,
130
17, 28
72
Master will generate and
process this variation
33
0
Frozen Analog Event - All
Variations
1
32-Bit Frozen Analog Event
Without Time
40
2
16-Bit Frozen Analog Event
Without Time
24
3
32-Bit Frozen Analog Event
With Time
88
4
16-Bit Frozen Analog Event
With Time
72
40
0
Analog Output Status - All
Variations
1
06
24
Master does not use this
object type and will not
generate a message or
process this type
1
32-Bit Analog Output Status
40
2
16-Bit Analog Output Status
129,
130
00, 01
24
41
0
Analog Output Block - All
Variations
24
1
32-Bit Analog Output Block
40
2
16-Bit Analog Output Block
3, 4, 5,
6
17, 28
129
Echo of
Request
24
Master will generate this
variation and parse the
response
50
0
Time and Date - All
Variations
48
1
Time and Date
2
07, With
Quant=
1
48
Master will generate this
variation
2
Time and Date With Interval
80
51
0
Time and Date CTO - All
Variations
1
Time and Date CTO
129,
130
07, With
Quant=
1
48
Master will process this
variation
2
Unsynchronized Time and
Date CTO
129,
130
07, With
Quant=
1
48
Master will process this
variation