ProSoft Technology MVI94-DNP User Manual
Page 112

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 112 of 131
ProSoft Technology, Inc.
December 17, 2010
OBJECT
REQUES
T
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits
)
NOTES
6
16-Bit Binary Counter
Without Flag
1, 7, 8, 9,
10
06
129,
130
00, 01
16
Slave will return this
variation (counter upper
16-bits removed)
7
32-Bit Delta Counter Without
Flag
129,
130
00, 01
32
Slave will return Unknown
Object to this request
8
16-Bit Delta Counter Without
Flag
129,
130
00, 01
16
Slave will return Unknown
Object to this request
21
0
Frozen Counter - All
Variations
1
06
32
Slave will return variation
9 data
1
32-Bit Frozen Counter
129,
130
00, 01
40
Slave will return Unknown
Object to this request
2
16-Bit Frozen Counter
129,
130
00, 01
24
Slave will return Unknown
Object to this request
3
32-Bit Frozen Delta Counter
40
Slave will return Unknown
Object to this request
4
16-Bit Frozen Delta Counter
24
Slave will return Unknown
Object to this request
5
32-Bit Frozen Counter With
Time Of Freeze
88
Slave will return Unknown
Object to this request
6
16-Bit Frozen Counter With
Time Of Freeze
72
Slave will return Unknown
Object to this request
7
32-Bit Frozen Delta Counter
With Time Of Freeze
88
Slave will return Unknown
Object to this request
8
16-Bit Frozen Delta Counter
With Time Of Freeze
72
Slave will return Unknown
Object to this request
9
32-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
32
Slave will return this
variation
10
16-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
16
Slave will return this
variation (counter upper
16-bits removed)
11
32-Bit Frozen Delta Counter
Without Flag
32
Slave will return Unknown
Object to this request
12
16-Bit Frozen Delta Counter
Without Flag
16
Slave will return Unknown
Object to this request
22
0
Counter Change Event - All
Variations
1
06, 07,
08
Slave will parse this
request and return no
data
1
32-Bit Counter Change
Event Without Time
129,
130
17, 28
40
Slave will return Unknown
Object to this request
2
16-Bit Counter Change
Event Without Time
129,
130
17, 28
24
Slave will return Unknown
Object to this request
3
32-Bit Delta Counter Change
Event Without Time
40
Slave will return Unknown
Object to this request