ProSoft Technology MVI94-DNP User Manual
Page 100

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 100 of 131
ProSoft Technology, Inc.
December 17, 2010
[DNP Slave
Analog
Inputs]
This section is used to override the default values of the class and
deadband assignments for the analog input points.
# Point# Class Deadband
START
This string signals the start of the point definition list.
6 1 2000 #points 0-5=class 1, deadband = 1000
7 1 2000
8 2 1000
END
This string signals the end of the point definition list.
Variable
Name
Description
[DNP Slave
Float Inputs]
This section is used to override the default values of the class and
deadband assignments for the float input points.
# Point# Class Deadband
START
This string signals the start of the point definition list.
0 1 100.
1 2 12.34
2 3 1.23
END
This string signals the end of the point definition list.
Variable
Name
Description
[DNP Slave
Double
Inputs]
This section is used to override the default values of the class and
deadband assignments for the double input points.
# Point# Class Deadband
START
This string signals the start of the point definition list.
0 1 100.
1 2 987.34
2 3 789.23
END
This string signals the end of the point definition list.