5.5
MVI94-DNP Configuration Forms
This section contains configuration forms that will aid in the configuration of the
module. If you design your system before trying to directly implement it, you will
have a greater chance of success. Fill in the configuration forms for your
application, and then edit the configuration text file. This section contains forms
for both master and slave configuration:
5.5.1 Slave Configuration
Variable
Name
Data
Range
Description
IF Error
Config.
Value
[Module]
This section header indicates the start of the module specific
parameter set.
Module Name: 80
Characters
This parameter sets the name or description
of the module’s application
"Not
Configured
"
Type:
M=Master
or S=Slave
This parameter must be set to M for the
DNP port to be used as a master port. If the
parameter is set to any other value, the port
will be used as a slave port.
S
Slave
Variable
Name
Data
Range
Description
IF Error
Config.
Value
[DNP Slave]
This section header defines the start of the DNP slave parameter set.
Internal Slave
ID:
0 to 65534 This is the DNP address for the module. All
messages with this address from the master
will be processed by the module.
65534
Baud Rate:
Baud Rate
from Table
Port Baud Rate: 300, 600, 1200, 2400,
4800, 9600, 19200, 384 (38400), 576
(57600), 115 (115200)
9600
RTS On:
0 to 65535 This value represents the number of 1 ms
increments to be inserted between
asserting the RTS modem line and the
actual transmission of the data.
NA
RTS Off:
0 to 65535 This value represents the number of 1 ms
increments to be inserted after the last
character of data is transmitted before the
RTS modem line is dropped.
NA
Min Response
Delay:
0 to 65535 Minimum time between receiving a request
and transmitting a response. Allows master
time to disable transmitter on an RS-485
network.
NA
Modem:
Y or N
This parameter defines if a dial-up modem
is used on the DNP slave port. If the value
is set to N, no modem is used. If the
parameter is set to Y, a modem is used.
N
Connect
Timeout:
0 to 65535 Defines the number of milliseconds to wait
for the CD signal to be set high. The CD
signal indicates a connection is made using
a dial-up modem.
NA