System Configuration Errors
Error Code Name
Description
100
Too many binary input
points
Too many binary input points are configured for the
module. Maximum value is 15360.
101
Too many binary output
points
Too many binary output points are configured for the
module. Maximum value is 15360.
102
Too many counter points
Too many counter points are configured for the
module. Maximum value is 480.
103
Too many analog input
points
Too many analog input points are configured for the
module. Maximum value is 960.
104
Too many analog input
points
Too many analog output points are configured for the
module. Maximum value is 960.
105
Too many binary input
events
Too many binary input events are configured for the
module. Maximum value is 400.
106
Too many analog input
events
Too many analog input events are configured for the
module. Maximum value is 400.
107
Invalid analog input
deadband
Deadband value for analog input events is out of
range. Value must be in the range of 0 to 32767.
108
Not enough memory
There is not enough memory in the module to
configure the module as specified.
109
Invalid block transfer delay
for blocks 251 and 252
(error/status blocks)
Block transfer delay value specified is too low.
110
File count invalid
The file count must be in the range of 0 to 6.
111
Invalid file record size
The file record size must be in the range of 1 to 120.
112
Invalid block identification
code for file
The file block transfer code must be in the range of
100 to 120.