ProSoft Technology MVI94-DNP User Manual
Page 96

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 96 of 131
ProSoft Technology, Inc.
December 17, 2010
Variable
Name
Data
Range
Description
IF Error
Config.
Value
First
Character
Delay:
0 to 65535 Defines the number of milliseconds to wait
before sending the first message after the
connection is first made. This delay only
applies to the first packet sent to the
modem.
NA
Redial Delay
Time:
0 to 65535 Defines the minimum number of
milliseconds to wait before a redial attempt
is made by the slave.
NA
Redial
Random
Delay:
0 to 65535 Defines a random millisecond time range to
be added to the redial delay time before the
modem is accessed.
NA
Idle Timeout:
0 to 65535 Defines the number of milliseconds the
modem is inactive before it will disconnect.
NA
Phone
Number:
ASCII
String Data
These fields contain a null-terminated,
ASCII character string used by the dial-up
modem. The string must contain all
characters required by the modem. An
example string is ATDT1800222333.
Maximum length is 34 bytes including the
terminating 0.
NA
Collision
Avoidance:
Y or N
This parameter defines if the collision
avoidance functionality is to be applied to
the port. If the parameter is set to N,
collision avoidance is not used. It will be
used if set to Y. If collision avoidance is
used, it requires a special cable.
N
CD Idle Time: 0 to 32000 Defines the minimum number of
milliseconds to wait before transmitting a
message after the CD signal is recognized
as low.
32000
CD Random
Time:
0 to 32000 Defines the range of random time to be
added to the CD Idle Time before a
message will be transmitted from the slave.
32000
CD Time
Before
Receive:
0 to 65535 Defines the number of milliseconds to wait
before receiving characters after the CD
signal is recognized as high.
NA
BI Class:
0 to 3
This parameter sets the default class
assignment for points in the binary input
dataset. All points not specified in the
override section of the configuration will be
assigned to this class. For class 0, no
events will be generated for the points.
0
AI Class:
0 to 3
This parameter sets the default class
assignment for points in the analog input
dataset. All points not specified in the
override section of the configuration will be
assigned to this class. For class 0, no
events will be generated for the points.
0
Float Class:
0 to 3
This parameter sets the default class
assignment for points in the float input
dataset. All points not specified in the
override section of the configuration will be
assigned to this class. For class 0, no
events will be generated for the points.
0