6.4.2 Level 1: Clearable Errors

Clearable errors are logged in the Event Log. They remain in the Active Error List

for 20 seconds, until the condition that caused the error is cleared (such as a

successful transfer after a retry), or until the scanner mode is changed from Stop

or Idle mode to Run mode.
Clearable errors include Trigger evaluation errors, Transfer List execution errors,

Time Sync source errors, and Time Sync destination errors.
Trigger evaluation errors include data read errors, data write errors and

evaluation overflow errors. If a Trigger evaluation error occurs, the Trigger will

be disabled for 5 seconds and then retried during a subsequent scan of the

Trigger.

Transfer List execution errors include: data read errors, data write errors and

data conversion errors. Transfer Lists can be configured with the following

error handling options.

Parameter

Description

Abort

Abort Transfer List on any Transfer error.

Continue

Abort the Transfer that generated the error, but continue Transfer List

execution.

Retry (default)

Retry the Transfer that generated the error until it succeeds.

Time Sync errors do not receive any special handling. The specified Time Sync

source or destination will be retried during the next scheduled Time Sync period.

6.4.3 Level 2: Warnings

Events at this level are serious warnings in the scanner that should be

investigated to determine their cause. These events are logged to the Event Log,

but do not appear in the Active Error List. An example of a Level 2 Warning is

"Configuration Server Client Connection Terminated Unexpectedly".

6.4.4 Level 3: Informational Events

Events at this level are significant events that have occurred in the scanner.

These events are logged to the Event Log, but do not appear in the Active Error

List. Three examples of Level 3 Informational Events are:
"Scanner Startup/Shutdown"
"Scanner Mode Change Requests"
"Service Thread Start/Stop"

6.4.5 Level 4 Verbose Informational Events

Events at this level are less significant events that have occurred in the scanner.

These events are logged to the Event Log, but do not appear in the Active Error

List. An example of a Level 4 Verbose Informational Event is "Configuration

Server Client Connection Established/Terminated Normally".