ProSoft Technology ILX56-MM User Manual
Page 74
Diagnostics and Troubleshooting
ILX56-MM ♦ ControlLogix Platform
User Manual
InRAx Message Manager for Industrial Communication
Page 74 of 112
ProSoft Technology, Inc.
February 6, 2012
See also Status, and Runtime Status
Runtime Transfer Lists Status
To open the Runtime Transfer Lists Status
page, click the S
TATUS
tab, then click
the R
UNTIME
tab, then click the T
RANSFER
L
ISTS
tab.
The Runtime Transfer Lists Status page contains a table that shows all of the
Transfer Lists that are defined in the scanner, along with information about each
Transfer List. The information about each Transfer List includes the following.
Parameter
Description
Count
Indicates the number of times the Transfer List has completed.
Error
Indicates the number of Transfer List I/O errors.
Exe Average
Average in milliseconds of the last 16 Transfer List execution times.
Exe Min
Minimum Transfer List execution time in milliseconds.
Exe Max
Maximum Transfer List execution time in milliseconds.
Size
The size of the transfer in bytes.
Error State Flag
This is set on the first encountered error and cleared on the next
successful Transfer List completion.
Source Status
Provides detailed status information such as Current Error, Recent
Error, Error History.
Destination Server
Provides detailed status information such as Current Error, Recent
Error, Error History.
To update the status while viewing the Runtime Transfer Lists Status page, click
the R
EFRESH
button.