Configure the ILX56-MM module

ILX56-MM ♦ ControlLogix Platform

User Manual

InRAx Message Manager for Industrial Communication

Page 54 of 112

ProSoft Technology, Inc.

February 6, 2012

Parameter

Description

Data Blocks

The memory that contains information for the program of the S7 PLC.
They may contain the following data types: BOOL, BYTE, WORD,

DWORD, INT, DINT, REAL, S5TIME, DATE, TIME, TIME_OF_DAY,

CHAR, DATE_AND_TIME, STRING, or ARRAY. Descriptions of these

data types should be available in the S7 PLC or Step 7 Programming

Software documentation. This memory is read/write for module access.

DB Number

The number of the desired Data Block to access. This field is only valid

if the Address Type selected is Data Blocks (DB).

Offset

The desired offset/number of the associated Address Type element.

The following is a description of this field’s meaning for each address

type:

Input,
Peripheral Input

& Output

Enter the slot number of the desired I/O module.

Flag Bit

Enter the byte offset within the Flag Bit memory of

the desired location.

Timers &

Counters

Enter the number of the desired timer or counter.

Data Blocks

Enter the number of the desired data block.

Bit ID

The desired bit number within the data element.

Data Type

The desired format for accessing the data. This field depends on the
selected Address Type. Certain Address Types have limited access and

particular Data Types will be grayed out if not applicable to the selected

Address Type.

String Size

The size of the string to be accessed. Enter the exact size of the string
as it is defined in the S7 PLC. This is only applicable to an Address

Type of STRING.

Click D

ONE

to close the Siemens S7 New Tag dialog box. Click the S

AVE

button

to save the new tag configuration data.
See also Tags.