ProSoft Technology ILX56-MM User Manual

Page 48

background image

Configure the ILX56-MM module

ILX56-MM ♦ ControlLogix Platform

User Manual

InRAx Message Manager for Industrial Communication

Page 48 of 112

ProSoft Technology, Inc.

February 6, 2012

Parameter

Description

Maximum Data Byte Gap The byte gap allowed in the reading of the register or coil data block.

Valid options are:

0

No gaps are allowed in the reg/coil data block.
Only sequential contiguous reg/coil read

requests may be combined in a request

message. For example, sequential reads of

Status Bits 10001 and 10003 will result in two

read request messages.

1

Scattered Coil (0x0000) and Status Bit (1x0000)

read requests with up to a 1 byte (8 bit) gap may
be combined in a single request message. For

example, sequential reads of 10001 and 10003

will result in a single request message with

10002 being discarded. Scattered sequential
Holding (4x0000) and Input (3x0000) register

accesses must be contained or exactly

adjacent.

8

Scattered sequential reg/coil read requests that
have up to an 8 byte gap may be combined in

the same read request message.

16

Scattered sequential reg/coil read requests that
have up to a 16 byte gap may be combined in

the same read request message.

32

Scattered sequential reg/coil read requests that
have up to a 32 byte gap may be combined in

the same read request message.

64

Scattered sequential reg/coil read requests that
have up to a 64 byte gap may be combined in

the same read request message.

128

Scattered sequential reg/coil read requests that
have up to a 128 byte gap may be combined in

the same read request message.

Single Register Writes

Determines if multiple or single register writes will occur. If this option is

"ON", 16-bit register writes will be executed one at a time, 32-bit writes
will be executed one at a time, and coil writes will be executed one at a

time. Array writes will require multiple messages to complete.

Timeout

The timeout value in milliseconds to be used in communicating with the

device.

You must be logged on as a user with Project or Administrator privilege to modify

the module data transfer configuration.
See also Configuration Editor, Tags