Conditions of Conformance

MST “Modular” products

When this product is used in applications governed by the requirements of the EEC, the following restric-
tions and conditions apply:

1. For European applications, requiring compliance to the Low Voltage Directive, 73/23/EEC, this power

supply is considered a component product, designed for “built in” applications. Because it is incom-
plete in construction, the end product enclosure must provide for compliance to any remaining electri-
cal safety requirements and act as a fire enclosure. (EN61010-1:2001 Cl. 6, Cl. 7, Cl.8, and Cl. 9)

2. This power supply is designed for stationary installation, with mains power applied via a KEPCO Rack

Adapter.

3. This power supply is considered a Class 1 (earthed) product. It is intended for use as part of equip-

ment meant for test, measurement and laboratory use, and is designed to operate from single phase,
three wire power systems. This equipment must be installed in a specifically designed KEPCO rack
adapter and within a suitably wired equipment rack, utilizing a three wire (grounded) mains connection.
See wiring section of this manual for complete electrical wiring instructions. (EN61010-1:2001
Cl.6.10.1)

4. This power supply has secondary output circuits that are considered hazardous.

5. The output wiring terminals of this power supply have not been evaluated for field wiring and, there-

fore, must be properly configured by the end product manufacturer prior to use.

6. This power supply employs a supplementary circuit protector in the form of a fuse mounted within its

enclosure. The fuse protects the power supply itself from damage in the event of a fault condition. For
complete circuit protection of the end product, as well as the building wiring, it is required that a pri-
mary circuit protection device be fitted to the branch circuit wiring. (EN61010-1:2001 Cl. 9.5)

7. Hazardous voltages are present within this power supply during normal operation. All operator adjust-

ments to the product are made via externally accessible switches, controls and signal lines as speci-
fied within the product operating instructions. There are no user or operator serviceable parts within
the product enclosure. Refer all servicing to qualified and trained Kepco service technicians.