beautypg.com

Table 2-3. rear terminations, 5 preliminary check-out, 1 required equipment – KEPCO MST Series User Manual

Page 21: 2 initial setup, Preliminary check-out -3, Required equipment -3, Initial setup -3, Rear terminations -3

background image

MST SERIES 061813

2-3

2.5

PRELIMINARY CHECK-OUT

2.5.1

REQUIRED EQUIPMENT

• Host computer w/communication cable for selected controller
• Kepco Controller (See PAR. 1.4.1).
• RA 55 or CA 400 rack adapter; alternative is to use Input Power/Communication Cable

(see Table 1-3)

• Load Interface Cable or mating load connector (see Table 1-3)
• Digital Voltmeter (DVM)
• Switch (SPST) rated 32V d-c, 1A

2.5.2

INITIAL SETUP

Initial set-up is as follows (See Figure 2-3):

1. Connect the Unit under test (UUT) to the computer/controller interface (refer to the appropri-

ate Controller Instruction Manual and to the Rack Adapter (RA 55 or CA 400) Instruction
Manual for source power connections). NOTE: An Alternative configuration using the Input
Power Communication cable in place of the rack adapter may be used.

2. Install the MST Power Module into a vacant rack adapter slot (see PAR. 2.6.2).

3. Configure the Load Interface Cable as shown in Figure 2-2. If the Load Interface Cable is not

available, wire load mating connector as shown in Figure 2-2.

FIGURE 2-2. DC OUTPUT CONNECTOR CONFIGURATION FOR PRELIMINARY CHECKOUT

CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to fault.

4. Apply a-c power first to the MST power module(s) by setting Power ON/OFF switch on front

panel to ON., then apply a-c power to the Controller.

5. Set switch S1 (Figure 2-3) to CLOSE SENSE position.

TABLE 2-3. REAR TERMINATIONS

REAR TERMINATION

FUNCTION

AC Input/Control Bus connector

Connects the MST Power Module to single-phase a-c power, safety ground, and two-
wire IEEE 1118 bi-directional Control Bus.

DC output connector

Connects the MST Power Module output lines, sensing lines, frame ground lines and
current share bus to the load.