beautypg.com

Section 3 - operation, 1 status flags (error messages), Table 3-1. error messages – KEPCO MST Series User Manual

Page 33: 2 timing requirements for a valid status, Status flags (error messages) -1, Timing requirements for a valid status -1, Error messages -1

background image

MST SERIES 061813

3-1

SECTION 3 - OPERATION

3.1

INTRODUCTION TO CONTROLLING THE MST POWER MODULE OUTPUT

The MST family of Power Modules is designed for remote operation only. Operating the power
supply requires a series of commands to be sent to the Power Module from a host computer, via
a selected IEEE 1118 bus compatible Controller (see PAR. 1.4.1). The commands may either be
pre-programmed or sent individually using a keyboard, depending upon the controller selected.

The MST Power Module responds to both SCPI (Standard Commands for Programmable
Instruments) and CIIL (Control Interface Intermediate Language) commands. SCPI and CIIL
provide a common language conforming to IEEE 488.2 for instruments. For an explanation of
SCPI and CIIL commands and program syntax, refer to the applicable controller Instruction
Manual.

3.1.1

STATUS FLAGS (ERROR MESSAGES)

The MST Power Module supplies information to the controller regarding its operating condition
when queried via the STAT:QUES:COND? command in SCPI, or via the STA command in CIIL.
A listing of the standard error messages for both SCPI and CIIL appear in the Instruction Manu-
als for the various Kepco Controllers (see PAR.1.4.1). Table 3-1 lists the “catastrophic” status
messages of both SCPI and CIIL, along with the related MST Power Module condition.

3.1.2

TIMING REQUIREMENTS FOR A VALID STATUS

After sending a command that might affect the output of the Power Modules or their relays, it is
recommended that the Status command be sent. For detailed information on this command
refer to the applicable controller Instruction Manual. For the Controller/MST system status com-
mand to be valid, the required time delay before sending the command is as follows:

• After an Open, Close (CIIL only), OUTP ON or OFF (SCPI only), Change of Polarity, or

Change of Mode, wait approximately 300 milliseconds.

TABLE 3-1. ERROR MESSAGES

CIIL ERROR MESSAGE

SCPI STATUS MESSAGE

POWER MODULE CONDITION

DEV Power Loss

POWER LOSS

OVERVOLTAGE / OVERCURRENT (See PAR. 3.7.2)
SOURCE POWER LOSS (See PAR. 3.7.4)

DEV Crowbarred

None

Not Supported

DEV Over Temperature

OVERTEMPERATURE

OVERTEMPERATURE (See PAR. 3.7.3)

DEV Overload

OVERLOAD

OPERATION IN MODE OTHER THAN PRO-
GRAMMED MODE (See PAR’s. 3.2.1, 3.2.2)

DEV Voltage Comparison Error

VOLTAGE ERROR

OUTPUT NOT AT PROGRAMMED VALUE

DEV Current Comparison Error

CURRENT ERROR

OUTPUT NOT AT PROGRAMMED VALUE

DEV Relay Not Opened
DEV Relay Not Closed
DEV Polarity Error

RELAY ERROR

DEFECT IN ISOLATION OR POLARITY RELAY
OPERATION

DEV Load Path Fault

RELAY ERROR

OPEN SENSE LEAD OR OPEN POWER LEAD
CONDITION (See PAR. 3.7.5)