beautypg.com

Table 1-2. mst general specifications, Mst general specifications -2 – KEPCO MST Series User Manual

Page 12

background image

1-2

MST SERIES 061813

.

TABLE 1-2. MST GENERAL SPECIFICATIONS

SPECIFICATIONS

RATING/DESCRIPTION

CONDITION

INPUT

A-C Voltage

nominal 100-250V a-c

Single phase

range 90-264 Va-c

Brownout Voltage

85Vrms

Frequency

nominal 50-60 Hz

At >63 Hz, input leakage current
exceeds specifications

range 47 – 63 Hz (400 Hz)

Input Current

maximum 3.6A rms

90V a-c Input

Current Harmonics

Within EN 61000-3-2 limits

Any source condition, rated load

Efficiency

minimum See Model Table 1-1

120V a-c, rated output Load

EMI

FCC Class A, CISPR 11 Class A

Conducted Emissions

Leakage Current

120V a-c,

60Hz

<0.5 mA

240V a-c,

50Hz

<1.0 mA

Power Factor

0.98 min.

All source conditions, full load

EMC

Complies with IEC 61326-1, Class A

OUTPUT

Source Effect

Voltage

0.001%

90 – 132, 176 – 264V a-c,
any load condition

Current

0.005%

Load Effect

Voltage

±0.002% or 0.5mV, whichever is greater

10% to 100% Load at EMAX,

any source condition

Current

±0.005%(1)

10% to 100% Load at IMAX

Temperature Effect

Voltage

0.01%/ °C

Any source/load condition

(0 – 45° C)

Current

0.02%/ °C

Time Effect (drift)

Voltage

0.01%

0.5 – 8.5 hours

Any source/load condition

Current

0.02%

Programming
Resolution

Voltage

12 Bits, 0.024%

% of EMAX

Current

12 Bits, 0.024%

% of IMAX

Data Read Back
Accuracy

Voltage

0.1%

% of EMAX

Current

0.12%

% of IMAX

Transient Recovery Time

100 Microseconds

(500 Microseconds for MST 6-20M)

Return to within stabilization
band from 50% load step

Turn On/Off Overshoot

None

Any source/load condition

Error Sense

0.5V maximum/wire

Any source/load condition

MISCELLANEOUS

Temperature

0 ° to +65° C, start from –20°C (see Table 1-1)

Operating

–40° to +85° C

Storage

Humidity

0 to 95% RH

Non-condensing Operating &
Storage

Shock

20G 11 msec ±50% half sine

3 axes, 3 shocks each axis,
non-operating

Vibration

5 – 10Hz 10mm double amplitude

Non-operating, 1 hour each axis

10 – 55 Hz 2G

Altitude

Sea level to 10,000 ft.

Any source/load condition

Isolation (Output – Case)

±500 V d-c

Display

Voltage 3.5 Digit LED, red

Front panel,

For reference only

Current 3.5 Digit LED, red

(1) Current mode regulation is subject to an additional 0.015% settling effect as well as a d-c offset of up to 3mA based on compli-
ance voltage