Specifications, General – Precision Digital PD6300 User Manual
Page 9

Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
9
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Main display: 0.6" (15 mm) high, red LEDs 
Second display: 0.46" (12 mm) high, red LEDs 
6 digits: each (-99999 to 999999), with lead zero blanking. 
DISPLAY 
INTENSITY 
Eight user selectable intensity levels
DISPLAY 
UPDATE RATE 
Rate: 10 per second; up to 1 per 100 seconds (and is a 
function of Low Gate setting) 
Total: 10 per second (fixed) 
OVERRANGE
Display flashes
999999
DISPLAY 
ASSIGNMENT 
The main (Big) and small (Little) displays may be assigned 
to rate, total, grand total, alternate rate & total, max/min, 
units (small display only), set points, and Modbus input. 
PROGRAMMING 
METHODS 
Four front panel buttons, digital inputs, PC and MeterView Pro 
software, Modbus registers, or cloning using Copy function. 
RECALIBRATION All ranges are calibrated at the factory to read frequency in
Hz. No recalibration required.
MAX/MIN 
DISPLAY 
Max/min readings reached by the process are stored until 
reset by the user or until power to the meter is turned off. 
PASSWORD
Three programmable passwords restrict modification of 
programmed settings and two prevent resetting the totals. 
Pass 1: Allows use of function keys and digital inputs 
Pass 2: Allows use of function keys, digital inputs and editing set/reset points 
Pass 3: Restricts all programming, function keys, and digital inputs. 
Total: Prevents resetting the total manually 
Gtotal: Prevents resetting the grand total manually
NON-VOLATILE 
MEMORY 
All programmed settings are stored in non-volatile memory 
for a minimum of ten years if power is lost. 
POWER 
OPTIONS 
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max 
or jumper selectable 12/24 VDC 
 10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow 
blow; up to 6 meters may share one 5 A fuse 
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals P+ & P-: 24 VDC
 10% @ 200 mA max (standard),
(12/24 VDC powered models rated @ 100 mA max). 
5 or 10 VDC @ 50 mA max, selectable with internal jumper J4. 
ISOLATION
4 kV input/output-to-power line 
500 V input-to-output or output-to-P+ supply 