Precision Digital PD6300 User Manual
Page 25
Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
25
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when
switching inductive loads to prevent disrupting the microprocessor’s op-
eration. The suppressors also prolong the life of the relay contacts. Sup-
pression can be obtained with resistor-capacitor (RC) networks assem-
bled by the user or purchased as complete assemblies. Refer to the fol-
lowing circuits for RC network assembly and installation:
C
R
C
R
Figure 12: AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1
for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check
to confirm proper operation.
3.
Install the RC network at the meter's relay screw terminals. An RC
network may also be installed across the load. Experiment for best
results.
Figure 13: Low Voltage DC Loads Protection
RC Networks Available from Precision Digital
RC networks are available from Precision Digital and should be applied
to each relay contact switching an inductive load. Part number:
PDX6901.
Note:
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Use a diode with a reverse
breakdown voltage two to
three times the circuit vol-
tage and forward current at
least as large as the load
current.