Relay operation details – Precision Digital PD6300 User Manual
Page 61
Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
61
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarm and control functions. These capa-
bilities include front panel alarm status LEDs as well as either 2 or 4 op-
tional internal relays and/or 4 external relays expansion module. Typical
applications include high or low flow alarms and basic batch control.
There are four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2.
Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Alternation Control for up to 8 Relays
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm
relays will reflect the state of the input to the meter. The following table
indicates how the alarm LEDs and relays will react on power-up based
on the set and reset points:
Alarm #
HI or LO
Alarm
Set
Point
Reset
Point
Power-Up
Reading
Relay &
LED
1 HI
1000
500 499 Off
2 LO
700
900 499 On
3 LO
250
400 499 Off
4 HI
450
200 499 On
Fail-Safe Operation
The following table indicates how the relays behave based on the fail-
safe selection for each relay:
Fail-Safe
Selection
Non-Alarm State
Alarm State
Power Failure
NO NC NO NC
Off Open
Closed
Closed
Open
Relays go to
non-alarm state
On Closed
Open
Open
Closed
Relays go to
alarm state
Note: NO = Normally Open, NC = Normally Closed. This refers to the
condition of the relay contacts when the power to the meter is off.