Aout, Dis 1, Dis 2 – Precision Digital PD6300 User Manual
Page 66: Out 1, Out 2
Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
66
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal
for any display range selected.
No equipment is needed to scale the analog output; simply program the
display values to the corresponding mA output signal.
The Analog Output menu is used to program the 4-20 mA output based
on display values.
Aout
Setup
dis 1
Aout
0
0000.0
d i s 1
dis 2
Aout
1
000.0
d i s 2
Out 1
Aout
0
4.000
O u t 1
Out 2
Aout
2
0.000
O u t 2
For instructions on how to program
numeric values see Setting Numer-
ic Values
, page 36.