Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a stan-
dard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an
RS-232 or RS-422/485 adapter option is required; see Ordering Informa-
tion
on page 8 for details.
Warning!
Do not connect any equipment other than Precision
Digital’s expansion modules, cables, or meters to the
RJ45 M-LINK connector. Otherwise damage will occur
to the equipment and the meter.
Note: More detailed instructions are provided with each optional serial
communications adapter.
Note: Refer to the PD6000/PD7000 Modbus Register Tables located at
www.predig.com for details.
baud
Serial
SlavId
Serial
tr dly
Serial
serial
t-byt
Serial
Parity
Serial
When using more than one meter in a multi-drop mode, each meter must
be provided with its own unique address. The meter address (Slave ID)
may be programmed between 1 and 247. The transmit delay may be set
between 0 and 199 ms. The parity can be set to even, odd, or none with
1 or 2 stop bits.
The PD6300 can also be connected to another PD6300 with a special
PDA1200 cable, allowing the user to copy all the settings from one meter
to another, using the Copy function.