Precision Digital PD6300 User Manual
Page 76
Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
76
Multi-Point Linearization
(Linear)
Meters are set up at the factory for linear function with 2-point lineariza-
tion. Up to 32 linearization points can be selected under the linear func-
tion.
The multi-point linearization can be used to linearize the display for
non-linear signals.
Program
Number of
Points
Linear
Functn
no Pts
L i n e a r
sCALE
S e l e c t
Square Root Linearization (Square)
Note: Although this option may appear in the menu the functionality is
not available in the PD6300 series products.
Programmable Exponent Linearization (Prog E)
Note: Although this option may appear in the menu the functionality is
not available in the PD6300 series products.
Round Horizontal Tank Linearization (rHt)
Note: Although this option may appear in the menu the functionality is
not available in the PD6300 series products.
!
Caution!
Attempting to program any of the three functions noted
above may affect any multi-point linearization
previously programmed.