beautypg.com

20 ma output connections, Analog output transmitter power supply – Precision Digital PD6300 User Manual

Page 26

background image

Model PD6300 Pulse Input Rate/Totalizer

Instruction Manual

26

4-20 mA Output Connections

Connections for the 4-20 mA transmitter output are made to the connec-
tor terminals labeled MA OUT. The 4-20 mA output may be powered
internally or from an external power supply.

12-35 VDC

Power

Supply

+

4-20 mA

Input Meter

-

+

R

I-

I+

1

3

2

RELAY1

3

2

1

24 V

-

4-20 mA Input

Remote Display,

Chart Recorder, Etc.

-

+

R

I-

I+

MA OUT

1

3

2

RELAY1

3

2

1

24 V

MA OUT

Figure 14: 4-20 mA Output Connections

Analog Output Transmitter Power Supply

The internal 24 VDC power supply powering the analog output may be
used to power other devices, if the analog output is not used. The I+
terminal is the +24 V and the R terminal is the return. This power supply
is capable of sourcing up to 40 mA.