Troubleshooting tips – Precision Digital PD6300 User Manual
Page 88
Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
88
Troubleshooting Tips
Symptom Check/Action
No display at all
Check power at power connector
Not able to change setup or pro-
gramming, Locd is displayed
Meter is password-protected, enter
correct six-digit password to unlock
Meter displays error message
during calibration (Error)
Check:
1. Signal
connections
2.
Minimum input span requirements
Meter displays
999999
-99999
Check:
1. Input
selected
in
Setup menu
2.
Corresponding signal at Signal
connector
Display is unstable
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3.
Filter and gate values
Display response is too slow
Check filter and gate values
Display reading is not accurate
Check:
Scaling or calibration
Display does not respond to input
changes, reading a fixed number
Check:
Display assignment, it might be dis-
playing max, min, or set point.
Display alternates between
1.
Hi
and a number
2.
Lo
and a number
Press Menu to exit max/min display
readings.
Relay operation is reversed
Check:
1. Fail-safe
in
Setup menu
2. Wiring of relay contacts
Relay and status LED do not
respond to signal
Check:
1. Relay
action
in
Setup menu
2.
Set and reset points
Flashing relay status LEDs
Relays in manual control mode or relay
interlock switches opened.
Meter not communicating with
application programs
Check:
1.
Serial adapter and cable
2. Serial
settings
3.
Meter Slave ID and baud rate
If the display locks up or the meter
does not respond at all
Cycle the power to reboot the
microprocessor.
Other symptoms not described
above
Call Technical Support for
assistance.