Installing the Hardware

64

Enterasys X-Pedition 8000/8600 Getting Started Guide

gauge negative (-) wires are connected to the X-Pedition 8600 DC power supply wiring block. See

Figure 28

.

Figure 28. Splitting each source wire to two 12-gauge wires

An alternate method of wiring the X-Pedition 8600 power supply is to use a single set of 8-AWG
wires (+ and -) from the DC source, and then tie the X-Pedition 8600’s wiring lugs together: + to +
and - to -. See

Figure 29

.

Figure 29. Tying X-Pedition 8600 DC supply lugs together

From 

-

 48-Volt 

Source

From 

+

 48-Volt

Source

Conductive 

Splitter Block

Conductive 

Splitter Block

12-Gauge Wire (Black)

6-Gauge Wire (Black)

6-Gauge Wire (Red)

12-Gauge Wire (Red)

+

+

-

-

12-Gauge Wire (Black)

12-Gauge Wire (Red)

XP-8600 

Wiring Lugs

From True 

Ground

8-Gauge Wire (Green)

Both positive (+) and both

negative (-) lugs are tied

together with 8-gauge wire

To True

Ground

(Green)

From Power

Source

(Black)

From Power

Source +

(Red)

8-Gauge Wire