2 status messages on lcd display, Status messages on lcd display -10, Status messages on lcd display – Emerson Process Management Bristol ControlWave ExpressPAC User Manual
Page 78
ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)
5-10
Service & Troubleshooting
Revised Mar-2011
Figure 5-5. WD and IDLE LEDs
The Ethernet port connector (J1) on the CPU/System Controller board
contains two LEDs that indicate transmit (yellow) and receive (green)
activity when lit.
5.3.2 Status Messages on LCD Display
If your unit includes the optional LCD display, you may see the
following status codes.
Table 5-1. LCD Status Codes
LCD Display
Indication / Explanation
Blank Application
running
DIAG
Unit in diagnostic mode
R DIAG
Unit running diagnostics
FWXSUM
Flash XSUM Error
DEVERR
Error initializing application device
FLASH
Flash programming error
FACT
Using factory defaults (flashed at startup)
BATT
Battery failure detected
STRTUP
Currently loading the boot project
WD LED
IDLE LED