2.3 Configuring the CPU/System Controller Board
To configure the CPU/System Controller board, you need to set some
switches and jumpers.
S1
1
2
3
4
1
23
45
6
7
8
1
2
3
4
5
6
RJ-45
W3 - 1-2 = Battery Enabled
2-3 = Battery Disabled
W2 - 1-2 = COM2 CTS from Port
W5 - 1-2 = 12/24V Power Supply
Shut-down Hysterisis
Shut-down Hysterisis
2-3 = 6V Power Supply
W6 - 1-2 = 12V Power Supply
Shut-down
Shut-down
2-3 = 6/24V Power Supply
2-3 = COM2 CTS to RTS
W1 - 1-2 = COM1 CTS from Port
2-3 = COM1 CTS to RTS
SW3 - COM3 Config.
RS-485 Receiver Biasing & Termination
2-Wire, 4-Wire Selction
J5 - COM3
Piggy-back
Radio Intf.
J3 - I/OBUS
Intf. to
CPU Board
P1
WE
J7
MSP430
JTAG
Header
J9
PLD JTAG
Header
J8
Emulation
Header
J3
J5
W1
4
W1
6
W7
W1
F3
W2
W3
W8
W6
W5
W1
5
W1
2
W1
3
Pulse
Input
LCD/
Keypad
CAUTION:
Damage WILL occur to
the CPU if the Ethernet
network is conected
to connector J2!
Power
Power In +
Aux. Power Out +
Solar Pwr. In +
GND
GND
GND
Solar Pwr. In and Aux. Power Out
are not available on units equipped
with an Ethernet Port.
Ultra Low Power & Low Power
CPU/System Controller Bds.
Don’t have an Ethernet Port.
NOTE:
1
5
6
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
1
2
3
4
5
TXD-/TXD
GND
RXD+
RXD-/RXD
Input
Input
Output
Output TXD+
4
1
2
3
GND
PULSE 1
PULSE 2
Input
Input
Output PULSE
PWR
COM2
RS-232
COM1
RS-232
Configuration
Options
Switch
Recovery
Mode &
COM./Status
LEDs
1
O
N
2
3
4
O
N
12
3
4
56
7
8
Receive LED
Transmit LED
10/100
Base-T
Ethernet
Port
TXD
GND
DCD
RXD
DTR
DSR
RTS
CTS
TXD
GND
DCD
RXD
Input
Input
Output
Output
Output
Input
Input
Input
Input
Output
Output
Output
Input
Input
DTR
DSR
RTS
CTS
RTD
Input
1
2
3
RTD-
RTD EXC
RTD+
COM3
RS-232
RS-485
W12 - W16 - 1-2 = COM3 RS-232
2-3 = COM3 RS-485
W7 - 1-2 = 12/24V Power Fail
Trip Point Hysterisis
Trip Point Hysterisis
2-3 = 6V Power Fail
W8 - 1-2 = 12V Power Fail
Trip Point
Trip Point
2-3 = 6/24V Power Fail
Trip Point
W17: 6/12V CPUs
1-2 = 6V S.P. Charging System
2-3 = 12V S.P. Charging System
W17: 12/24V CPUs
1-2 = 12V S.P. Charging System
2-3 = N/A
Note: W17 is N/A on 24V Systems
Do NOT connect a 24V Solar
Panel to TB-1 & TB-2!
NOTE:
J7, J8, J9
Factory Use
W17
2 = Watchdog
1 = Idle
}
CR1
CR1
2
1
Do Not Connect a 24V Solar Panel
to Connector TB1-1 & TB1-2!
RJ-45
1
2
6
Power
GND
Sec. Battery Input
3 2 1
T
X
D
R
X
D
G
N
D
COM1
RS-232
W18
W18: COM1 connector
selection
1 to 2 = J4 active
2 to 3 = J11 active
Figure 2-6. - CPU/System Controller Board Component I.D. Diagram