beautypg.com

6 non, On tb4 of process i/o board – Emerson Process Management Bristol ControlWave ExpressPAC User Manual

Page 57

background image

ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)

3.3.6 Non-Isolated High Speed Counter (HSC) / Discrete Inputs (DI)

on TB4 of Process I/O Board

Process I/O board connector TB4 provides interface to two internally
sourced single-ended high speed counter/discrete inputs (HSC1 and
HSC2).

Table 3-8. Non-Isolated High Speed Counter/Discrete Inputs General
Characteristics

Type Number

Supported

Characteristics

High Speed
Counter /
Discrete Inputs

2 on TB4

of Process

I/O board

Surge suppression and signal

conditioning.

HSCs can use dry contacts or open

collector field circuits.

High speed counter switch-selectable

frequency of 10kHz or 300Hz.

Sourced from 3.3Vdc and switch

selectable for a source current of
200μA (switch SW1-3 = OFF) or
2.2mA (switch SW1-3 = ON). Note:
These switches affect all DIs and
HSCs.

Wiring See Figure 3-2 for wiring diagrams.

Switch Settings See Table 3-2 for details on setting switches.

Software Configuration To use data from these high speed counter/discrete inputs you must

include a CWM_EIO board in your ControlWave project using
ControlWave Designer’s I/O Configurator, and then configure it. See
the ControlWave Designer Programmer's Handbook (D5125) for more
information. That same manual includes an I/O Mapping section that
describes, for advanced users, the I/O map for this board. To read a DI
value, look at the appropriate offset for the _STATE variable for the
board.

Revised Mar-2011

I/O Configuration and Wiring

3-11