beautypg.com

Appendix a - specifi cations, A-1 inverter/charger specifi cations – Magnum Energy RD Series User Manual

Page 50

background image

Page 44

©

2010 Magnum Energy, Inc.

Appendix A - Specifi cations

Appendix A - Specifi cations and Optional Equipment

A-1 Inverter/Charger

Specifi cations

RD2212

RD1824

RD2824

RD3924

Inverter Specifi cations

Input Battery Voltage Range

9 to 16 VDC

18 to 32 VDC

18 to 32 VDC

18 to 32 VDC

Absolute Maximum DC Input

25 VDC

35 VDC

35 VDC

35 VDC

AC Output Voltage Accuracy

120 VAC ±5% (≤ continuous power)

Output Frequency and Accuracy

60 Hz ± 0.1 Hz

Continuous Power Output (at 25° C)

2200 VA

1800 VA

2800 VA

3900 VA

1 msec Surge Current (amps AC)

60

70

100

150

100 msec Surge Current (amps AC)

37

40

60

90

5 sec Surge Power (real watts)

3700

4000

6000

9000

30 sec Surge Power (real watts)

3450

3300

4800

6400

5 min Surge Power (real watts)

3100

2850

3950

5800

30 min Surge Power (real watts)

2400

2400

3500

4750

Maximum Continuous Input Current

293 ADC

120 ADC

186 ADC

260 ADC

Inverter Effi ciency (peak)

95%

94%

93%

93%

HBCO/HBCI (High Battery Cut Out/In)

≥15.8 VDC

≥31.6 VDC

≥31.6 VDC

≥31.6 VDC

LBCO/LBCI (Low Battery Cut Out/In)

9 VDC (adj)/12.5 VDC

18 VDC (adj)/25 VDC

18 VDC (adj)/25 VDC

18 VDC(adj)/25 VDC

Series Stacking 120/240 VAC

No

Transfer Time

16 msecs

Search Mode (typical)

5 watts

No Load (120 VAC output, typical)

20 watts

12 watts

19 watts

25 watts

Waveform

Modifi ed Sine Wave

Charger Specifi cations

Continuous Output at 25°C

110 ADC

50 ADC

80 ADC

105 ADC

Input Current - Rated Output (AC amps)

15

15

21

29

Charger Effi ciency

85%

85%

85%

92%

AC Input Frequency Range

50 to 70 Hz

AC Input Voltage Range

60 to 140 VAC (120 VAC nominal)

Power Factor

> 0.95

General Features and Capabilities

Transfer Relay Capability

Two input legs at 30A each, or combine for 60A

Five-stage Charging Capability

Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™

Battery Temperature Compensation

Yes, 15 ft Battery Temp Sensor standard

Internal Cooling

0 to 120 cfm variable speed drive using dual 92 mm brushless DC fan

Overcurrent Protection

Yes, with two overlapping circuits

Over-temperature Protection

Yes, on transformer, MOSFETS, and battery

Corrosion Protection

PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners

Safety Listings

ETL listed to UL1741

Warranty

2 years parts and labor

Dual Branch-Rated Output Breakers

No

Environmental Specifi cations

Operating Temperature

-20°C to +60°C (-4°F to 140°F)

Non-operating Temperature

-40°C to +70°C (-40°F to 158°F)

Operating Humidity

0 to 95% RH non-condensing

Physical Specifi cations

Unit Dimensions (h x w x d)

13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3 cm)

Shipping Dimensions (h x w x d)

18.5” x 17.5” x 12.5” (47 cm x 44.5 cm x 31.8 cm)

Mounting

Shelf (top or bottom up) or wall (no uncovered vents on top or bottom)

Unit Weight

37 lb (16.8 kg)

35 lb (15.9 kg)

42 lb (19.1 kg)

53 lb (24 kg)

Shipping Weight

42 lb (19.1 kg)

40 lb (18.1 kg)

47 lb (21.3 kg)

58 lb (26.3 kg)

Max operating altitude

15,000’ (4570 m)

Specifi cations @ 25°C - Subject to change without notice.