Page 33

Installation

8. Even though the light bulb is on, the inverter is currently disabled (off). Press and release the

ON/OFF switch on the inverter to enable (turn-on) the inverter.

9. Disconnect the incoming AC power to the inverter. Verify the light bulb remains on and is

now powered by the inverter.

If the inverter passes all the previous steps, the inverter is ready for use. If the inverter fails any

of the steps, refer to the Troubleshooting section.

Figure 2-20, AC Voltage Checks

A C T erm in al B lo ck

A C O u tp u t

120 V ac

( ± 5% )

N eu tral to G ro u n d

< 0.5 V ac

3 0

30

Info: The inverter’s AC output voltage will not be correct until a load greater than

5 watts (5 watts is the default setting) is connected to the inverter; or, when the

Search Mode is turned OFF with a remote display (ME-RC50).

5. Check the AC output voltage of the inverter by connecting an AC voltmeter to the output

terminals (see Figure 2-20) and verify the correct output voltages.

6. Press and release the inverter’s ON/OFF switch to turn the inverter off. The inverter’s status

indicator and the connected load should go off.

7. Apply AC power to the inverter’s AC input. After the AC input power is qualifi ed (approximately 15

seconds), the incoming AC power will transfer through the inverter to the inverter’s AC output and

power the light bulb. Verify the inverter’s status indicator and that the light bulb comes on.