Installation
2.5.6
AC Wiring Confi guration
The following table provides the different wiring confi gurations for installing and connecting the
AC conductors into and out of the inverters (see Figures 2-11 to 2-14 for installation diagrams
showing these confi gurations).
Table 2-3, AC Input/Output Wiring Confi gurations
SI/SO
(30A)
Single In/
Single Out
(30A)
SI/SO (60A)
Single In/
Single Out
(60A)
DI/SO
Dual In/
Single Out
DI/DO
Dual In/
Dual Out
AC Source
1
Required
120 VAC @
< 30 amps
120 VAC @
> 30 amps
(60 amps
maximum).
120/240 VAC (or
2 separate legs
of 120 VAC)
@ < 30 amps
per leg
120/240 VAC (or
2 separate legs
of 120 VAC)
@ < 30 amps per
leg
Reason to
Use
Have an 120
VAC source
that is < 30
amps.
Requires
a separate
inverter
sub-panel.
Have an 120
VAC source
that is > 30
amps.
Requires
a separate
inverter
sub-panel.
Want dedicated
charging and
dedicated pass-
thru while the
AC source is on.
Requires a
separate inverter
sub-panel.
May need to
power 240 VAC
loads when
AC source is
on (requires
120/240 VAC
source).
Requires a
separate inverter
sub-panel.
Appropriate
Models
RD2212
RD1824
RD2824
RD3924
RD2212
RD1824
RD2824
RD3924
RD2212
RD1824
RD2824
RD3924
RD2212
RD1824
RD2824
RD3924
Maximum
Input
Breaker
Required
-
Minimum
Wire Size
30A
(single pole)
-
#10 AWG
(In & Out)
60A
(single pole)
-
#6 AWG
(In & Out);
Can be split to
two #10 AWG
(for HOT 1
& HOT 2)
30A
(dual pole)
-
#10 AWG
(In & Out)
30A
(dual pole)
-
#10 AWG
(In & Out)
Maximum
Inverter
Pass-thru
capacity
3600W
(30A @
120 VAC)
7200W
(60A @
120 VAC)
3600W
(30A @
120 VAC)
7200W
(2 legs of 30A @
120/240 VAC or
2 legs of 30A @
120 VAC)
2
Wiring
Diagram
Figure 2-11
Figure 2-12
Figure 2-13
Figure 2-14
Note 1: AC Source is from either utility power or a generator.
Note 2: If two legs of 30A @ 120 VAC are used, they must be from the same source.