Installation

Table 2-2, DC Wire Size For Increased Distance (in free air)

Inverter

Model

Minimum Recommended DC Wire Size (one way)

*

1-3 feet

3-5 feet

5-10 feet

RD2212

#4/0 AWG (107.16 mm

2

) #4/0 AWG x2 (107.16 mm

2

)

not recommended

RD1824

#2/0 AWG (67.4 mm

2

)

#2/0 AWG (67.4 mm

2

)

#4/0 AWG (107.16 mm

2

)

RD2824

#4/0 AWG (107.16 mm

2

)

#4/0 AWG (107.16 mm

2

)

#4/0 AWG x2 (107.16 mm

2

)

RD3924

#4/0 AWG (107.16 mm

2

) #4/0 AWG x2 (107.16 mm

2

)

not recommended

* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).

2.4.3

DC Cable Connections

Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal

part of the inverter’s DC terminal. When connecting the DC cable to the battery or inverter DC

terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly

installed hardware causes a high resistance connection, which could lead to poor inverter/charger

performance and may melt the cable and terminal connections.
Follow the examples in Figures 2-5 and 2-6 to connect the DC cables and stack the hardware

correctly. Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).

CAUTION: The DC terminal and Kep nuts are made of stainless steel, which has a high

likelihood of seizure. To help prevent the bolt and nut from seizing — causing the bolts

to strip or snap/break-off — the use of anti-seize lubricant is highly recommended.

Info: If antioxidant grease or spray is used, apply it after all the connections have been

made and are properly tightened.

Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Kep nuts.

Figure 2-5, Battery Hardware

Installation

Figure 2-6, Inverter DC Hardware

Installation

battery cable

(w ith ring lug)

nut

split

w asher

flat

w asher

Battery

T em perature

Sensor

battery

post

C A U T ION:

Ensure nothing is

placed betw een

the cable ring lug

and the battery

post.

5/16 -18"

F lange or

Kep nut

battery cable

(w ith ring lug)

Inverter D C

term inal

(5/16 -18" bolt,

5/8" length)

C A U T ION:

Ensure nothing is

placed betw een

the D C term inal

and the ring lug.