beautypg.com

Installation – Magnum Energy RD Series User Manual

Page 21

background image

©

2010 Magnum Energy, Inc

Page 15

Installation

2.4.1

DC Wire Sizing

It is important to use the correct DC wire to achieve maximum effi ciency from the system and

reduce fi re hazards associated with overheating. Always keep your wire runs as short as practical

to help prevent low voltage shutdowns and keep the DC breaker from nuisance tripping (or open

fuses) because of increased current draw. See Table 2-1 to select the required minimum DC wire

size (and corresponding overcurrent device) based on your inverter model. The cable sizes listed

in Table 2-1 for your inverter model are required to reduce stress on the inverter, minimize voltage

drops, increase system effi ciency, and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery bank is greater than 5 feet (1.5 m), the DC wire

size will need to be increased. Longer distances cause an increase in resistance, which affects the

performance of the inverter. Continue to use the overcurrent device previously determined from

Table 2-1, and then refer to Table 2-2 to determine the minimum DC wire size needed for various

distances based on your inverter model.

2.4.2

DC Overcurrent Protection

DC overcurrent protection is not included in the inverter, it must be provided as part of the

installation. This requirement is needed in order to comply with electrical code regulations and

for safety reasons. The DC overcurrent protection device must be installed in the positive DC

cable line, it can be a fuse or a circuit breaker, and it must be DC rated. It must be correctly sized

according to the size of DC cables being used, which means it is required to open before the cable

reaches its maximum current carrying capability, thereby preventing a fi re. The NEC requires both

overcurrent protection and a disconnect switch. If a circuit breaker is used as the overcurrent

protection device, it can also be used as the required DC disconnect.
If a fuse is used as an overcurrent device, a Class-T type or equivalent is recommended. This fuse

type is rated for DC operation, can handle the high short-circuit currents, and has a time delay

that allows for momentary current surges from the inverter without opening the fuse. However,

because the fuse can be energized from both directions, if it is accessible to unqualifi ed persons

the NEC requires that it be installed in such a manner that the power must be disconnected on

both ends of the fuse before servicing.
The recommendations in Table 2-1 may not meet all local code or NEC requirements.

Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use

Inverter Model

Maximum

Continuous

Current

1

Using Conduit

DC Grounding

Electrode

Wire Size

4

Minimum DC Wire

Size (90°C rating)

2

Maximum DC

Breaker Size

3

RD2212

293 amps

#4/0 AWG

[107.2 mm

2

]

(260 amps)

250 amps

#6 AWG

(13.3 mm

2

)

RD1824

120 amps

#2/0 AWG

[67.4 mm

2

]

(195 amps)

175 amps

#6 AWG

(13.3 mm

2

)

RD2824

186 amps

#4/0 AWG

[107.2 mm

2

]

(260 amps)

250 amps

#6 AWG

(13.3 mm

2

)

RD3924

260 amps

#4/0 AWG

[107.2 mm

2

]

(260 amps)

250 amps

#6 AWG

(13.3 mm

2

)

Note 1 - Maximum Continuous Current is based on the inverter’s continuous power rating at the lowest input

voltage with an ineffi ciency factor.

Note 2 - Wire size is based on the requirements needed to increase effi ciency and reduce stress to the inverter.

Note 3 - The next larger standard size overcurrent device may be used if the de-rated cable ampacity falls between

the standard overcurrent devices found in the NEC.

Note 4 - Per the NEC, the DC grounding electrode conductor can be a #6 AWG (33.6 mm2) conductor if that is the

only connection to the grounding electrode and that grounding electrode is a rod, pipe, or plate electrode.

Note 5 - May not allow continuous operation at full rated power as defi ned by the NEC.

This manual is related to the following products: