3.4 Transfer

Time

While in Standby Mode, the AC input is continually monitored. Whenever AC power falls below the

VAC dropout voltage (80 VAC, default setting), the inverter automatically transfers back to the

Inverter Mode with minimum interruption to your appliances – as long as the inverter is turned

on. The transfer from Standby Mode to Inverter Mode occurs in approximately 16 milliseconds.

While the RD Series is not designed as a computer UPS system, this transfer time is usually fast

enough to hold them up. However, the VAC dropout setting has an effect on the ability of the

loads to transfer without resetting. The lower this setting, the longer the effective transfer will be

and therefore, the higher the probability for the output loads to reset. This occurs because the

incoming AC voltage is allowed to fall to a level that is so low that when the transfer does occur,

the voltage on the inverter’s output has already fallen to a level low enough to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators

with an unstable output) may nuisance transfer. This commonly happens when powering loads that

are larger than the generator can handle – causing the generator’s output voltage to constantly

fall below the inverter’s input VAC dropout threshold.

Info: When switching from Inverter Mode to Standby Mode, the inverter waits

approximately 15 seconds to ensure the AC source is stable before transferring.

3.5 Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the battery temperature around

the batteries. This information allows the multi-stage battery charger to automatically adjust the

battery charge voltages for optimum charging performance and longer battery life.
When the BTS is installed, if the temperature around the BTS is below 77°F (25°C) the absorb and

fl oat charge voltage increases, and if the temperature around the BTS is higher than 77°F (25°C),

the absorb and fl oat charge voltage decreases. See Figure 3-4

to determine how much the charge

voltage changes (increases or decreases) depending on the temperature reading of the BTS. For

example, the nominal absorb charge voltage for a fl ooded battery at 77°F (25°C) on a 24-volt

model is 29.2 VDC. If the battery temperature is 95°F (35°C), the absorb charge voltage would

decrease to 28.6 VDC (29.2 VDC - 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be compensated and the

battery will maintain the charge it had at a temperature of 77°F (25°C). The life of the batteries may

be reduced if they are subjected to large temperature changes when the BTS is not installed.

Info: When the BTS is connected, the battery charger uses a value of 5mV/°C/Cell

from 0-50°C to change the charge voltage based on temperature.

-0.75

-0.6

-0.45

-0.3

-0.15

0

0.15

0.3

0.45

0.6

0.75

0

5

1 0

1 5

2 0

2 5

3 0

3 5

4 0

4 5

5 0

Tem perature reading from BTS

T em p eratu re C o m p en satio n u sin g B T S

0C

32F

5C

41F

10C

50F

45C

113F

30C

86F

40C

104F

35C

95F

25C

77F

20C

68F

15C

59F

50C

122F

C

ha

ng

e to

b

a

tte

ry

c

h

ar

g

in

g

v

o

lta

g

e

no B TS

c onnec ted

12 V D C units

+0.75 V

+0.6 V

+0.45 V

+0.3 V

+0.15 V

N o C hange

-0.15V

-0 .3V

-0.45V

-0 .6V

-0.75V

24 V D C units

+1.5 V
+1.2 V
+0.9 V
+0.6 V
+0.3 V

N o C hange

-0 .3V
-0 .6V
-0 .9V
-1 .2V
-1 .5V

Figure 3-4, BTS Temperature to Charge Voltage Change