Appendix C - Preventive Maintenance

Appendix C - Preventive Maintenance

Recommended Inverter and Battery Care

The MM Series inverter is designed to provide you with years of

trouble-free service. Even though there are no user-serviceable parts,

it is recommended that every 6 months you perform the following

maintenance steps to ensure optimum performance and extend the

life of your batteries.

WARNING: Prior to performing these checks, switch both

the AC and DC circuits OFF.

• Visually inspect batteries for cracks, leaks, or swelling – replace if

necessary.

• Use baking soda to clean and remove any electrolyte spills or

buildups.

• Check and tighten all battery hold down clamps.
• Clean and tighten (10 to 12 foot-pounds) all DC terminals (battery

and inverter) and connecting cables.

• Check and fi ll battery water levels (Liquid Lead Acid batteries

only).

• Check individual battery voltages (replace those that vary more

than 0.3 VDC of each other).

• Check all cable runs for signs of chafi ng – replace if necessary.
• Check the inverter’s cooling vents – clean as necessary.

RV/Marine Off-Season Storage

When placing your coach or boat into seasonal storage, it is recom-

mended that you perform the following to ensure the system is prop-

erly shut down (or properly confi gured for seasonal storage). This is

especially important for maintaining the batteries.

• Perform the recommended maintenance steps noted above.
• Fully charge the batteries.
• Connect shore power (if available) and verify that the breaker to

the battery charger is switched ON.

• Verify the inverter is switched OFF.
• Switch OFF all unnecessary AC and DC loads.