Battery Bank Wiring

WARNING: Lethal currents will be present if the positive

and negative cables attached to the battery bank touch

each other. During the installation and wiring process,

ensure the cable ends are insulated or covered to prevent

touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery bank to

the inverter until: 1) all DC/AC wiring complete, 2) the cor-

rect DC and AC overcurrent protection have been installed,

and 3) the correct DC voltage and polarity have been verifi ed.

Info: For optimum performance, a minimum battery bank

of 200 AHr is recommended.

Depending upon the type of batteries you use in the installation (6

or 12 VDC), the batteries must be wired in series, parallel, or series-

parallel to provide 12 VDC (see Appendix B - Battery Information, for

guidance on wiring batteries together). The interconnecting DC wires

must be sized and rated exactly the same as those that are used be-

tween the battery bank and the inverter.

Place the batteries as close as practical to the inverter, preferably in

an insulated and ventilated enclosure. Allow adequate space above the

batteries to access the terminals and vent caps (as applicable). Also,

allow at least 1” of space between the batteries to provide good air

fl ow. DO NOT mount the batteries directly under the inverter.

Info: To ensure the best performance from your inverter

system do not use old or untested batteries. Batteries

should be of the same size, type, rating, and age.
CAUTION: Install batteries in a well ventilated area. Bat-

teries can produce explosive gasses. For compartment or

enclosure installations, always vent batteries to the outside.

Inverter to Battery Bank Wiring

WARNING: Ensure all sources of DC power (i.e., bat-

teries, solar, wind, or hydro) and AC power (utility/shore

power or AC generator) are de-energized (i.e., breakers

opened, fuses removed) before proceeding.
CAUTION: The inverter is NOT reverse polarity protected.

If this happens, the inverter will be damaged and will not

be covered under warranty.

Before connecting the DC

wires from the batteries to the inverter, verify the correct

battery voltage and polarity using a voltmeter. If the posi-

tive terminal of the battery is connected to the negative

terminal of the inverter and vice versa, severe damage will

result. If necessary, color code the cables with colored tape

or heat shrink tubing; RED for positive (+), and BLACK for

negative (-) to avoid polarity confusion.