Ac in ac out, Ac ground in/out, Neutral in – Magnum Energy MM612 Inverter User Manual

Page 25: Hot out, Neutral out, Hot in

background image

©

2010 Magnum Energy, Inc.

AC IN

AC OUT

Strain

reliefs

AC

Ground

In/Out

(green)

Neutral

In

(white)

Hot

Out

(red)

Neutral Out

(white w/black

stripe)

Hot

In

(black)

Figure 11, AC Wiring Connections

AC Input Wiring
Your inverter has an AC transfer feature that passes the AC input

power to the inverter’s output. Connection to the AC input is made by

hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from

the AC distribution panel) through a strain relief on the AC IN open-

ing. Refer to Table 4 for minimum wire size and overcurrent protection

required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC cable,

and then separate the three wires and strip about 3/4” of insulation

from each wire.
3. Using approved AC wire connectors, connect the incoming Hot In,

Neutral In, and Ground wires to the MM Series’ AC wires colored black

(HOT IN), white (NEU IN), and green (AC GROUND) respectively.
4. After making the AC input connections, secure the AC input cable

by tightening the strain relief.
The AC input wiring in the inverter is complete. Review all AC wiring to

ensure all connections are correct and secure.

19

2.0 Installation