2.0 Installation

18

The AC wires inside the AC compartment are #16 AWG with a tem-

perature rating of 105° C, all AC connections should be made using an

approved connector for your application (e.g., split bolt, twist-on wire

connectors, etc.). Ensure the wire connectors used are rated for the

size and number of wires you are connecting.
After connecting the wires together, gently pull on the wires to ensure

they are securely held together. In a proper connection, no bare wire

should be exposed

.

Info: Per UL certifi cation, non-metallic sheathed cable (i.e.,

Romex™) or a SO fl exible cord with listed strain reliefs

are allowed to be used to connect to the inverter; conduit

connections are not allowed.

AC Wire Size and Overcurrent Protection

The AC input and output wiring must be sized

per the NEC and

lo-

cal electrical safety code requirements

to ensure the wire’s ability to

safely handle the inverter’s

maximum load current. After determining

the proper AC wire sizes, the inverter’s AC input (unless you are using

a fl exible cord) and output wires are required to be protected against

overcurrent and have a means to disconnect the AC circuits.
Overcurrent protection must be provided by fuses or circuit-breakers,

and must

be properly sized and rated for the wire they are protecting

and the appliances being powered.

An external disconnect device is required for both the AC input and AC

output wiring. Most inverter’s that are “hardwired” use a service/distri-

bution panel wired to the inverter’s input (main panel), and a dedicat-

ed panel between the inverter’s output wiring and the AC loads (sub-

panel). These systems use the circuit breakers provided in the panels

as the overcurrent protection and the AC disconnect. If fuses are used,

then separate AC disconnect switches will be needed.
Based on information from the NEC, Table 4 provides the minimum AC

wire size and the suggested breaker size based on the inverter model.

H

owever, larger wire size may be required because of voltage drop.

The

AC wire sizes provided in this table assume using only copper wire

and a temperature rating of 75° C or higher. A minimum of #14 AWG

is required for all AC wiring.

After all AC wiring in the inverter is complete — prior to reattaching

the AC access cover — review all wiring to ensure all connections are

correct and secure.

Table 4, Minimum Wire Size to Circuit-breaker Size

Inverter

Model

AC Input

AC Output

Input

Breaker

Minimum

Wire Size

Suggested

Breaker Size

Output

Breaker

Minimum

Wire Size

Suggested

Breaker Size

MM612

7 amps

#14 AWG

10 amps

8 amps

#14 AWG

10 amps

MM1212

20 amps

#12 AWG

20 amps

12 amps

#14 AWG

15 amps