3.0 Operation

Factory Default Settings

Your MM Series inverter uses default settings that are adequate for

most installations. However, if you determine that some of your oper-

ating parameters need to be changed, the optional ME-RC50 remote

allows you to control the operation and to customize the programming

parameters of the inverter and/or charger.

Table 5, Inverter Default Settings

To help you determine if you need the ME-RC50 remote*, information

on the settings that can be changed is provided below. The settings

once programmed are saved in non-volatile memory and will be pre-

served until changed – even if DC power to the inverter is lost (the

ME-RC50 must always be connected).
Search Watts: This setting allows you to enable the power-saving

Search Mode circuitry and to adjust the power level at which the

inverter will “wake up” and start inverting. This function is not

available on the MM612 model and is adjusted to 5W (“wakes up” and

inverts if loads exceed 5 watts) on the MM1212.

LBCO: This setting determines when the inverter will turn off based

on low battery voltage (inverter turns off automatically after battery

voltage has been below this setting for more than one minute). This

protects the batteries from over-discharge and the AC loads from

unregulated power (brown-outs).
Battery AmpHrs: This setting allows the user to input the battery

bank size in amp hours, which provides information to the charger on

how long to charge the batteries in the Absorb Charging stage.
Battery Type: Sets the type of batteries being used in the system

which provides information to the charger to determine what voltage

level to charge the batteries.
Charge Rate: This setting uses a percentage of the charger’s max.

output to determine the output charge rate. This setting can be used

to limit the amount of current that the charger can use (leaving more

current available to power loads); or, to ensure small battery banks

are not overheated because of a charge rate that is too high.

VAC Dropout: Sets the min. AC voltage that can be present on the

AC input before the unit transfers from Transfer Mode to Invert Mode.

This protects the AC loads from utility outages and brown-outs.
* Visit our website (www.magnumenergy.com) for more information.

Function

Default Settings

Search Watts

NA (MM612),

5W (MM1212)

LowBatCutOut

10.0 VDC

Battery AmpHrs

400 AmpHrs

(Absorb Time = 120 minutes)

Battery Type

Flooded - Liquid Lead Acid

(Bulk = 14.6 VDC,

Float = 13.4 VDC)

Charge Rate

100%

VAC dropout

80VAC