DC Overcurrent Protection

For safety and to comply with electrical code regulations, you must

install a DC overcurrent protection device in the positive DC cable

line to protect your DC cables. This DC overcurrent device must be

DC rated and can be a fuse or circuit-breaker. It must be correctly

sized according to the size of DC cables being used, which means it

is required to open before the cable reaches its maximum current

carrying capability, thereby preventing a fi re.

See Table 1 to select

the DC overcurrent device needed based on the minimum wire size

according to your inverter model.

Electrical systems in mobile installations typically do not require

using a DC disconnect, although an overcurrent protection device is

still required. Because the DC disconnect is not required, a fuse is

usually used as the overcurrent device in these installations. These

installations also do not normally use conduit, so the fuse

must be

installed

in the ungrounded conductor (usually the positive DC cable

line)

within 18 inches of the battery – to protect the DC wiring system.

If using a fuse, we recommend using a

class-T type or equivalent. This

fuse type is rated for DC operation, can

handle the high short-circuit

currents, and

allows for momentary current surges from the inverter

without opening.

DC Grounding
The inverter/charger should always be connected to a permanent,

grounded wiring system.

The idea is to connect the metallic chassis

of the various enclosures together to have them at the same voltage

potential, which reduces the possibility for electric shock.

For the

majority of installations, the inverter chassis and the negative battery

conductor are connected to the system’s ground bond via a safety-

grounding conductor (bare wire or green insulated wire) at only one

point in the system. Per the NEC, the size for the grounding conductor

is usually based on the size of the overcurrent device used in the DC

system.

Refer to Table 1

to select the appropriate DC ground wire

based on the overcurrent device used for your inverter model.

If using this inverter in a vehicle, DO NOT connect the battery negative

(-) cable to the vehicle’s safety ground. Connect it only to the invert-

er’s negative battery terminal. If there are any non-factory installed

DC appliances on board the vehicle, DO NOT ground them at the safety

ground. Ground them only at the negative bus of the DC load center

(as applicable).