2.0 Installation

8

Locating and Mounting the Inverter

WARNINGS:
• Do not mount the inverter near any fl ammable or com-

bustible fl uid or components.
• Provide adequate clearance/ventilation to the inverter.
• Mount only on a “non-combustible” surface.
• Maximum ambient temperature around the inverter must

not exceed 77° F (25° C) to meet power specifi cations.

The inverter should only be installed in a location that meets the

following requirements:
Clean and Dry - The inverter should not be installed in an area that

allows

dust, fumes, insects, or rodents to enter or block the inverter’s

ventilation openings. This area also must be free from any risk of

condensation, water,

or any other liquid that can enter or fall on the

inverter. The inverter uses stainless steel fasteners, plated copper

busbars, and a power-coated aluminum base. Also, the internal circuit

boards are conformal coated. The above measures are undertaken

to help fi ght the harmful effects of corrosive environments. However,

the life of the inverter is uncertain if used in any of these types of

environments, and inverter failure under these conditions is not

covered under warranty.
Cool - The inverter should be

protected from direct exposure to the

sun or any equipment that produces extreme heat.

The ambient air

temperature should be between 32° F (0° C) and 104° F (40° C);

realize that the inverter’s output specifi cations are rated at 77° F (25°

C), so the cooler the better within this range.

Ventilated - In order for the inverter to provide full output power and

avoid over-temperature fault conditions; do not cover or block the

inverters ventilation openings, or install this inverter in an area with

limited airfl ow. Allow as much clearance around the inverter’s intake

and exhaust ventilation openings as possible, see Items 12 and 13 in

Figure 3. At the minimum, allow an airspace clearance of 6” (15 cm) at

the front and back, and 3” (7.5 cm) everywhere else to provide ad-

equate ventilation.

If installed in an enclosure, a fresh air intake opening must be pro-

vided directly to the front side (intake vent) and an exhaust opening

on the back side (exhaust vent) of the inverter. This will allow cool air

from the outside to fl ow into the inverter, and heated air to exit away

from the inverter and the enclosure. When mounted in an enclosed

compartment, airfl ow must be at least 59 cfm in order to maintain no

more than a 68° F (20° C) rise in compartment temperature. Minimum

clearances can be reduced if airfl ow is increased, but in no case should

clearance around the inverter be less than 2” (5 cm) on all sides.
Safe - Keep any fl ammable/combustible material (e.g., paper, cloth,

plastic, etc.) that may be ignited by heat, sparks, or fl ames at a

minimum distance of 2 feet (60 cm) away from the inverter.