beautypg.com

Remote transfer to bypass, Smoke purge operation, Multi-function digital inputs – Yaskawa E7L Drive Bypass User Manual

Page 48

background image

Electrical Installation 2 - 16

Remote Transfer to Bypass

Terminal TB1-4 on the Control PCB A2 is a dedicated terminal for “Remote Transfer” to Bypass operation.

This function allows a contact closure from a BAS, between terminals TB1-4 and TB1-9, to transfer motor operation from
Drive mode to Bypass mode. This remote transfer to Bypass function overrides the Drive Select manual button. An open

contact causes operation in Drive mode and a closed contact results in Bypass mode.

Smoke Purge Operation

Terminal TB1-5 on the Control PCB A2 is a dedicated terminal for “Smoke Purge” operation.

This function allows a contact closure between terminals TB1-5 and TB1-9 to transfer motor operation to Bypass for a

maximum capacity smoke control function. When in smoke purge mode, during emergency fire/smoke situations, the motor
overloads and safety interlock circuit are overridden to shift the priority to protecting people rather than equipment.

[Note: Smoke purge overrides all other control inputs and selector buttons. Smoke purge operation can only be terminated by
opening the contact closure at terminal TB1-5 or by opening the disconnect switch (S1 on schematic E7L-00).]

Multi-Function Digital Inputs

The Bypass 120 VAC logic circuit is interconnected with the Drive multi-function digital input terminals to allow a single

customer interface to control both Drive and Bypass circuits.

As a result, only Drive digital input terminals S6 and S7 are available for other uses. Drive Terminals S6, S7 and SN have been
brought out to TB5-5, TB5-4 and TB5-2 respectively. See Appendix A and Chapter 5, parameter H1-04 and H1-05 for

programming instructions.