Preventive maintenance, Table 7.3 preventive maintenance, Maintenance 7 - 3 – Yaskawa E7L Drive Bypass User Manual
Page 205

Maintenance 7 - 3
Preventive Maintenance
If the Drive is used under the following conditions, it may be necessary to inspect more often:
• High ambient temperatures, humidity or altitudes above 3,300 feet
• Frequent starting and stopping
• Fluctuations of the AC power supply or load
• Excessive vibration and/or shock loading
• Poor environment, including dust, metal particles, salt, sulfuric acid, chlorine
Table 7.3 Preventive Maintenance
Inspection Points
Item
Check Points
Every 3-6 Months
Yearly
General
Environment
Ambient Temperature
Humidity
Dust
Harmful Gas
Oil Mist
Equipment
Abnormal vibration or noise
AC Power Supply
Main circuit & control voltage
AC Power Circuit &
Devices
Conductors & Wire
Connections
Loose lugs, screws & wires
Hot spots on parts
Corrosion
Bent conductors
Breakage, cracking or discoloration
Check spacing
Transformers & Reactors
Discoloration or Noise
Terminal Blocks
Loose, damaged
DC Bus Capacitors
Leakage
Ruptures, broken, expansion
Capacitance & insulation resistance
Relays & Contactors
Noisy
Contact discoloration
Soft Charge Resistors
Cracked
Discoloration
Control Circuits
Operation
Speed reference voltage/current
I/O contact operation
Relay logic
Cooling System
Cooling Fans/Fins & Heatsink
Abnormal fan noise
Loose connectors
Free of accumulation
Keypad/Front Panel
Display
Digital Operator and
Front Panel
LEDs
Monitor display values
Key and selector switch functionality
Clean