O2-08, Cumulative operation time, Selection – Yaskawa E7L Drive Bypass User Manual
Page 237: Elapsed time run, Sets how time is accumulated for the elapsed timer, O2-07), Power-on time, Time accumulates whenever drive is powered), Running time, Time accumulates only when drive is running)

Parameters A - 25
o2-08
Cumulative Operation Time
Selection
Elapsed Time Run
Sets how time is accumulated for the elapsed timer
(o2-07).
0: Power-On Time
(Time accumulates whenever drive is powered)
1: Running Time
(Time accumulates only when drive is running)
0 or 1
1
Programming
o2-09
Initialization Specification
Selection
Init Mode Sel
Determines parameter values after a drive initialization
(A1-03) is executed. This should always be set to "1"
American Spec.
1: American spec
2: European spec
4: PV-A spec
5: PV-E spec
6: Chinese spec
1 to 5
1
Programming
o2-10
Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set
Sets the initial value of the heatsink fan operation time.
0 to 65535
0 hours
Programming
o2-12
Fault Trace/Fault History Clear
Function
FLT Trace Init
Clears the fault memory contained in the U2 and U3
monitors.
0: Disabled (no effect)
1: Enabled - resets U2 and U3 monitors, and returns
o2-12 to zero
0 or 1
0
Programming
o2-14
kWh User Monitor (U1-29)
Initialization
kWh MonitorClear
Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to
zero.
0 or 1
0
Programming
o2-15
Hand Key Function Selection
Oper Hand Key
Enables or disables the "Hand" key on the digital
operator.
0: Disabled
1: Enabled
0 or 1
1
Programming
COPY Function
o3-01
Copy Function Selection
Copy Function Sel
This parameter controls the copying of parameters to
and from the digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from
the drive to the digital operator.
2: OP -> INV WRITE - All parameters are copied from
the digital operator into the drive.
3: OP<-->INV VERIFY - Parameter settings in the drive
are compared to those in the digital operator.
NOTE: When using the copy function, the drive model
number and software number (U1-14) must match or an
error will occur.
0 to 3
0
Programming
o3-02
Read Allowed Selection
Read Allowable
Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are
allowed
1: Enabled - Copying allowed
0 to 1
0
Programming
Auto-Tuning
T1-02
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kW.
NOTE: T1-02 should be left at the Drive default (the last
3 digits of the Drive model number).
0.00 to
650.00
kVA
Dependent
Auto-Tuning
T1-04
Motor Rated Current
Rated Current
Sets the motor rated current.
(Used only during an auto-tune).
kVA
Dependent
kVA
Dependent
Auto-Tuning
Table A.1 Parameter List (Continued
)
Parameter
No.
Parameter Name
LCD Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location