Programming 5 - 59
H3-13 Master Frequency Reference Terminal Selection
Parameter H3-13 allows the programmer to select which analog input will serve as the Speed Command input when “Termi-
nals” are selected as the Auto Mode Speed source (b1-01= “1: Terminals”), or Terminal is selected as the reference source for
the Hand mode (b1-12= “1: Terminals”). For the A2 analog input to be an effective selection for the H3-13 parameter, param-
eter H3-09 must be configured as Aux Reference (H3-09= “2: Aux Reference”).
If H3-09
≠2, then the A1 analog input will be used regardless of the setting of parameter b1-12.
Setting
Description
0
Main Fref= A1 (factory default)
1
Main Fref= A2