beautypg.com

Bypass model number and enclosure style, Table 1.1 bypass, Physical installation 1 - 2 – Yaskawa E7L Drive Bypass User Manual

Page 14

background image

Physical Installation 1 - 2

Bypass Model Number and Enclosure Style

The Bypass covers two voltage ranges: 208-240 VAC and 480 VAC. Ratings applicable are from 1/2 to 60 HP.

Table 1.1 Bypass

Voltage

Bypass

Base Model Number

HP

Bypass

Continuous

Output

Current

(Amps)

Uses

Basic Drive

Model

-

Number

NEMA 1

*NEMA 12

FVFF

208 VAC

E7LVD002

E7LBD002

0.5

2.4

CIMR-E7U22P2

E7LVD003

E7LBD003

0.75

3.5

CIMR-E7U22P2

E7LVD004

E7LBD004

1

4.6

CIMR-E7U22P2

E7LVD007

E7LBD007

2

7.5

CIMR-E7U22P2

E7LVD010

E7LBD010

3

10.6

CIMR-E7U22P2

E7LVD016

E7LBD016

5

16.7

CIMR-E7U23P7

E7LVD024

E7LBD024

7.5

24.2

CIMR-E7U27P5

E7LVD030

E7LBD030

10

30.8

CIMR-E7U27P5

E7LVD046

E7LBD046

15

46.2

CIMR-E7U2011

E7LVD059

E7LBD059

20

59.4

CIMR-E7U2015

E7LVD074

E7LBD074

25

74.8

CIMR-E7U2018

240 VAC

E7LVA002

E7LBA002

0.5

2.2

CIMR-E7U22P2

E7LVA003

E7LBA003

0.75

3.2

CIMR-E7U22P2

E7LVA004

E7LBA004

1

4.0

CIMR-E7U22P2

E7LVA006

E7LBA006

2

6.8

CIMR-E7U22P2

E7LVA009

E7LBA009

3

9.6

CIMR-E7U22P2

E7LVA015

E7LBA015

5

15.2

CIMR-E7U23P7

E7LVA022

E7LBA022

7.5

22

CIMR-E7U25P5

E7LVA028

E7LBA028

10

28

CIMR-E7U27P5

E7LVA042

E7LBA042

15

42

CIMR-E7U2011

E7LVA054

E7LBA054

20

54

CIMR-E7U2015

E7LVA068

E7LBA068

25

68

CIMR-E7U2018

E7LVA080

E7LBA080

30

80

CIMR-E7U2022

480 VAC

E7LVB001

E7LBB001

0.5

1.1

CIMR-E7U42P2

E7LVB001

E7LBB001

0.75

1.6

CIMR-E7U42P2

E7LVB002

E7LBB002

1

2.1

CIMR-E7U42P2

E7LVB003

E7LBB003

2

3.4

CIMR-E7U42P2

E7LVB004

E7LBB004

3

4.8

CIMR-E7U42P2

E7LVB007

E7LBB007

5

7.6

CIMR-E7U43P7

E7LVB011

E7LBB011

7.5

11

CIMR-E7U45P5

E7LVB014

E7LBB014

10

14

CIMR-E7U47P5

E7LVB021

E7LBB021

15

21

CIMR-E7U4009

E7LVB027

E7LBB027

20

27

CIMR-E7U4011

E7LVB034

E7LBB034

25

34

CIMR-E7U4015

E7LVB040

E7LBB040

30

40

CIMR-E7U4018

E7LVB052

E7LBB052

40

52

CIMR-E7U4024

E7LVB065

E7LBB065

50

65

CIMR-E7U4030

E7LVB077

E7LBB077

60

77

CIMR-E7U4037

* The Nema 12 FVFF Enclosure is ventilated and filtered with gaskets. UL does not recognize NEMA 12

ventilated enclosures, therefore, for UL purposes, these units are designated NEMA 1.