beautypg.com

Error check – Yaskawa E7L Drive Bypass User Manual

Page 259

background image

Communications D - 7

Error Check

Errors are detected during communication using CRC-16. Perform calculations using the following method:

1. The factory setting for CRC-16 communication is typically zero, but when using the Modbus system, set the factory setting

to one (e.g., set all 16 bits to 1).

2. Calculate CRC-16 using MSB as slave address LSB, and LSB as the MSB of the final data.
3. Calculate CRC-16 for response messages from the slaves and compare them to the CRC-16 in the response messages.