Point number, Point type, Point name – Yaskawa E7L Drive Bypass User Manual
Page 274: Factory default, Si units), Engr. units, Slope, Intercept, Text, Drive
Communications D - 22
Table D.13 APOGEE FLN Application 2721 Point Number Summary (Continued)
Point
Number
Point
Type
Point Name
Factory Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Drive
Parameter
{87}
LAI
PID OUT CAP
0
PCT
0.01
0
–
–
U1-37
{88}
LAI
PID REF
0
PCT
0.01
0
–
–
U1-38
{89}
LAI
COM ERR CD
0
–
1
0
–
–
U1-39
90
LDO
COM FLT ENA
DISABLE
–
1
0
ENABLE
DISABLE
H5-05
91
LAO
CBL LOSS FRQ
0
HZ
0.01
0
–
–
d1-04
92
LAO
CBL LOSS TMR
2
SEC
0.1
0
–
–
H5-09
{93}
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
U1-12 (Bit 7)
{94}
LDO
RESET FAULT
NO
–
1
0
RESET
NO
–
{95}
LDI
DRV COM ERR
NO FLT
–
1
0
FAULT
NO FLT
–
{96}
LDO
EXTERNAL FLT
OK
–
1
0
FAULT
OK
–
{97}
LDI
MF IN 5 MON
OFF
–
1
0
ON
OFF
U1-10 (Bit 6)
{99}
LAI
ERROR STATUS
0
–
1
0
–
–
–
This manual is related to the following products: