Metasys N2 Analog Output (AO) Summary
Table D.10 Metasys N2 Analog Output Summary (Metasys N2 to E7)
Object ID
Object Name
Units
Default Value
E7 Parameter
AO 1
SPEED COMMAND
0.01 Hz
-
AO 2
ACCELERATION TIME
SEC
30.0
C1-01
AO 3
DECELERATION TIME
SEC
30.0
C1-02
AO 4
PI PROPORTIONAL GAIN
-
2.00
b5-02
AO 5
PI INTEGRAL TIME
SEC
5.0
b5-03
AO 6
STALL PREVENTION LEVEL – RUN
%
120
L3-06
AO 7
STALL PREVENTION LEVEL – ACCEL
%
120
L3-02
AO 8
REFERENCE OPERATION MODE SELECT
-
1
b1-01
AO 9
RUN OPERATION MODE SELECT
-
1
b1-02
AO 10
PI MODE SELECT
-
0
b5-01
AO 11
FREQUENCY COMMAND UPPER LIMIT
% of MAX
100.0
d2-01
AO 12
FREQUENCY COMMAND LOWER LIMIT
% of MAX
0.0
d2-02
AO 13
MOTOR RATED CURRENT
A
Motor model dependent
E2-01
AO 14
JUMP FREQUENCY 1
0.1Hz
0.0
d3-01
AO 15
JUMP FREQUENCY 2
0.1Hz
0.0
d3-02
AO 16
JUMP FREQUENCY 3
0.1Hz
0.0
d3-03
AO 17
JUMP FREQUENCY BANDWIDTH
0.1Hz
1.0
d3-04
AO 18
NUMBER OF AUTO RESTARTS
-
0
L5-01
AO 19
OPERATOR DISPLAY MODE
-
0
o1-03
AO 20
POWER LOSS RIDE THROUGH
SEC
Drive model dependent
L2-02
AO 21
CABLE LOSS TIME-OUT
SEC
2.0
H5-09
AO 22
CABLE LOSS SPEED
0.01Hz
0.00
d1-04
AO 23
PI INTEGRAL LIMIT
0.1%
100.0
b5-04
AO 24
PI UPPER LIMIT VALUE
0.1
100.0
b5-06
AO 25
PI OFFSET ADJUSTMENT
0.1
0.0
b5-07
AO 26
PI PRIMARY DELAY TIME
0.01
0.00
b5-08
AO 27
PI FEEDBACK REFERENCE
MISSING DETECTION SELECT
1
0
b5-12
AO 28
PI FEEDBACK REFERENCE
MISSING DETECTION LEVEL
1%
0
b5-13
AO 29
PI FEEDBACK REFERENCE
MISSING DETECTION TIME
0.1 SEC
1.0
b5-14
AO 30
READ PARAMETER NUMBER
-
-
AO 31
WRITE PARAMETER NUMBER
-
-
AO 32
WRITE PARAMETER DATA
-
-