beautypg.com

Metasys n2 analog output (ao) summary, Communications d - 17 – Yaskawa E7L Drive Bypass User Manual

Page 269

background image

Communications D - 17

Metasys N2 Analog Output (AO) Summary

Table D.10 Metasys N2 Analog Output Summary (Metasys N2 to E7)

Object ID

Object Name

Units

Default Value

E7 Parameter

AO 1

SPEED COMMAND

0.01 Hz

-

AO 2

ACCELERATION TIME

SEC

30.0

C1-01

AO 3

DECELERATION TIME

SEC

30.0

C1-02

AO 4

PI PROPORTIONAL GAIN

-

2.00

b5-02

AO 5

PI INTEGRAL TIME

SEC

5.0

b5-03

AO 6

STALL PREVENTION LEVEL – RUN

%

120

L3-06

AO 7

STALL PREVENTION LEVEL – ACCEL

%

120

L3-02

AO 8

REFERENCE OPERATION MODE SELECT

-

1

b1-01

AO 9

RUN OPERATION MODE SELECT

-

1

b1-02

AO 10

PI MODE SELECT

-

0

b5-01

AO 11

FREQUENCY COMMAND UPPER LIMIT

% of MAX

100.0

d2-01

AO 12

FREQUENCY COMMAND LOWER LIMIT

% of MAX

0.0

d2-02

AO 13

MOTOR RATED CURRENT

A

Motor model dependent

E2-01

AO 14

JUMP FREQUENCY 1

0.1Hz

0.0

d3-01

AO 15

JUMP FREQUENCY 2

0.1Hz

0.0

d3-02

AO 16

JUMP FREQUENCY 3

0.1Hz

0.0

d3-03

AO 17

JUMP FREQUENCY BANDWIDTH

0.1Hz

1.0

d3-04

AO 18

NUMBER OF AUTO RESTARTS

-

0

L5-01

AO 19

OPERATOR DISPLAY MODE

-

0

o1-03

AO 20

POWER LOSS RIDE THROUGH

SEC

Drive model dependent

L2-02

AO 21

CABLE LOSS TIME-OUT

SEC

2.0

H5-09

AO 22

CABLE LOSS SPEED

0.01Hz

0.00

d1-04

AO 23

PI INTEGRAL LIMIT

0.1%

100.0

b5-04

AO 24

PI UPPER LIMIT VALUE

0.1

100.0

b5-06

AO 25

PI OFFSET ADJUSTMENT

0.1

0.0

b5-07

AO 26

PI PRIMARY DELAY TIME

0.01

0.00

b5-08

AO 27

PI FEEDBACK REFERENCE

MISSING DETECTION SELECT

1

0

b5-12

AO 28

PI FEEDBACK REFERENCE

MISSING DETECTION LEVEL

1%

0

b5-13

AO 29

PI FEEDBACK REFERENCE

MISSING DETECTION TIME

0.1 SEC

1.0

b5-14

AO 30

READ PARAMETER NUMBER

-

-

AO 31

WRITE PARAMETER NUMBER

-

-

AO 32

WRITE PARAMETER DATA

-

-