Communications D - 18
Metasys N2 Binary Input (BI) Summary
Metasys N2 Binary Output (BO) Summary
Table D.11 Metasys N2 Binary Input Summary (E7 to Metasys N2)
Object ID
Object Name
Default
Off (0) State
On (1) State
BI 1
RUN / STOP MONITOR
0
STOPPED
RUNNING
BI 2
FORWARD / REVERSE MONITOR
0
FORWARD
REVERSE
BI 3
DRIVE READY MONITOR
0
NOT READY
READY
BI 4
FAULT MONITOR
0
NOT FAULTED
FAULTED
BI 5
ZERO SPEED
0
NOT ZERO SPEED
ZERO SPEED
BI 6
SPEED AGREE
0
NOT SPEED AGREE
SPEED AGREE
BI 7
MINOR FAULT
0
NO MINOR FAULT
MINOR FAULT
BI 8
MAJOR FAULT
0
NO MAJOR FAULT
MAJOR FAULT
BI 9
DRIVE COMMUNICATION
ERROR MONITOR
0
NO ERROR
ERROR
BI 10
MULTI-FUNCTION OUTPUT 1 (H2-01)
0
-
-
BI 11
MULTI-FUNCTION OUTPUT 2 (H2-02)
0
-
-
BI 12
MULTI-FUNCTION OUTPUT 3 (H2-03)
0
-
-
BI 13
SAFETY INTERLOCK MONITOR
0
SAFETY CLEAR
TERMINAL 3 CLOSED
SAFETY SET
TERMINAL 3 OPEN
BI 14
HAND / AUTO REFERENCE MONITOR
0
REMOTE
LOCAL
BI 15
MULTI-FUNCTION INPUT 1 MONITOR
0
OFF
ON
BI 16
MULTI-FUNCTION INPUT 2 MONITOR
0
OFF
ON
BI 17
MULTI-FUNCTION INPUT 3 MONITOR
0
OFF
ON
BI 18
MULTI-FUNCTION INPUT 4 MONITOR
0
OFF
ON
BI 19
MULTI-FUNCTION INPUT 5 MONITOR
0
OFF
ON
Table D.12 Metasys N2 Binary Output Summary (Metasys N2 to E7)
Object ID
Object Name
Default
Off (0) State
On (1) State
BO 1
RUN FORWARD COMMAND
0
STOP
FORWARD
BO 2
RUN REVERSE COMMAND
0
STOP
REVERSE
BO 3
SERIAL FAULT (EF0) COMMAND
0
NO FAULT
FAULT
BO 4
FAULT RESET COMMAND
0
NO RESET
RESET
BO 5
MULTI-FUNCTION INPUT 1 (H1-01)
0
-
-
BO 6
MULTI-FUNCTION INPUT 2 (H1-02)
0
-
-
BO 7
MULTI-FUNCTION INPUT 3 (H1-03)
0
-
-
BO 8
MULTI-FUNCTION INPUT 4 (H1-04)
0
-
-
BO 9
MULTI-FUNCTION INPUT 5 (H1-05)
0
-
-
BO 10
PANEL LOCK
0
LOCAL/REMOTE AND
STOP/RESET KEYS
ENABLED
LOCAL/REMOTE AND
STOP/RESET KEYS
DISABLED
BO 11
COMMUNICATION FAULT ENABLE
0
EF0 NOT ACTIVATED IF
CABLE LOSS OCCURS
EF0 ACTIVATED IF
CABLE LOSS OCCURS