Parameters a - 25, Copy function, Auto-tuning – Yaskawa P7B Drive Bypass User Manual
Page 243: Table 1, Parameter list (continued

Parameters A - 25
o2-08
Cumulative Operation Time
Selection
Elapsed Time Run
Sets how time is accumulated for the elapsed timer
(o2-07).
0: Power-On Time (Time accumulates whenever Drive
is powered).
1: Running Time (Time accumulates only when Drive is
running)
0 or 1
1
Quick Setting
o2-09
Initialization Specification
Selection
Init Mode Sel
Determines parameter values after a Drive initialization
(A1-03) is executed. This should always be set to "1"
American Spec.
1: American spec
2: European spec
4: PV-A spec
5: PV-E spec
1 to 5
1
Programming
o2-10
Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set
Sets the initial value of the heatsink fan operation time.
0 to 65535
0H
Programming
o2-12
Fault Trace/Fault History Clear
Function
FLT Trace Init
Clears the fault memory contained in the U2 and U3
monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns
o2-12 to zero.
0 or 1
0
Programming
o2-14
kWh User Monitor (U1-29)
Initialization
kWH MonitorClear
Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change).
1: Clear all - Resets U1-29 to zero and returns o2-14
to zero.
0 or 1
0
Programming
o2-15
Hand Key Function Selection
Oper Hand Key
Enables or disables the "Hand" key on the digital
operator.
0: Disabled
1: Enabled
0 or 1
1
Programming
COPY Function
o3-01
Copy Function Selection
Copy Function Sel
This parameter controls the copying of parameters to
and from the digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from
the Drive to the digital operator.
2: OP -> INV WRITE - All parameters are copied from
the digital operator into the Drive.
3: OP<-->INV VERIFY - Parameter settings in the
Drive are compared to those in the digital operator.
NOTE: When using the copy function, the Drive
model number and software number (U1-14) must
match or an error will occur.
0 to 3
0
Programming
o3-02
Read Allowed Selection
Read Allowable
Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are
allowed.
1: Enabled - Copying allowed
0 to 1
0
Quick Setting
Auto-Tuning
T1-02
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kW.
NOTE: If motor power is given in horsepower, power
in kW can be calculated using the following formula:
kW = Hp * 0.746
0.00 to
650.00
kVA
Dependent
Auto-Tuning
T1-04
Motor Rated Current
Rated Current
Sets the motor rated current. (Used only during an auto-
tune).
kVA
Dependent
kVA
Dependent
Auto-Tuning
Table 1:
Parameter List (Continued
)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location